@@ -764,26 +764,29 @@ if (($MSmode == 5) or ($MSmode == 4))
|
|
|
// Post Regulation Current Monitor
|
|
|
|
|
|
$U_ist = abs($adeiValue[10][0]);
|
|
|
- $PR_hw_current = abs($adeiValue[10][31]);
|
|
|
- $I_PR = $PR_hw_current;//$I_ist - $I_noPR;
|
|
|
$APR_on = abs($adeiValue[10][29]);
|
|
|
- $P_PR = $U_ist * $I_PR/1000; // 28W limit, 33 kV mit 0,7 mA ist Maximum für stabilen Betrieb
|
|
|
+ $PID_setpoint = abs($adeiValue[10][30]);
|
|
|
+ $I_PR = abs($adeiValue[10][31]);
|
|
|
+ $P_PR = $U_ist * $I_PR/1000;
|
|
|
+
|
|
|
+ // low voltage U < 25 kV, high voltage up to 33 kV, not higher.
|
|
|
+ // set limits to make sure not to exceed 28W limit or 0.95 mA for low voltages
|
|
|
+ // at high voltages limit to 24W or 0,7 mA for stable operation
|
|
|
|
|
|
$pic = "postreg";
|
|
|
- if ($I_PR > 0.1)
|
|
|
+ if ($I_PR >= 0.1)
|
|
|
{
|
|
|
if ($I_PR < 0.46) {$pic = $pic."Warn";}
|
|
|
- else if (($I_PR >= 0.46) && ($I_PR <= 0.82)) {$pic = $pic."On";}
|
|
|
- else if ($I_PR > 0.8) {$pic = $pic."Alarm";}
|
|
|
+ else if (($I_PR >= 0.46) && ($I_PR <= 0.95) && ($P_PR < 28)) {$pic = $pic."On";}
|
|
|
+ else if (($I_PR > 0.95) | ($P_PR >= 28)) {$pic = $pic."Alarm";}
|
|
|
}
|
|
|
- else $pic = $pic."Off";
|
|
|
-
|
|
|
+ else $pic = $pic."Off";
|
|
|
|
|
|
$pos_y = 501;
|
|
|
$pos_x = 455;
|
|
|
|
|
|
$color = "#000000";
|
|
|
- placePic($pos_y,$pos_x, $pic.".png", 30, "Status of HV post regulation 
green = normal operation 
gray = off 
red = current too high 
orange = current too low");
|
|
|
+ placePic($pos_y,$pos_x, $pic.".png", 30, "Status of HV post regulation 
green = normal operation 
gray = off 
red = current or power too high 
orange = current too low");
|
|
|
|
|
|
if ($I_PR < 0.1)
|
|
|
{
|
|
@@ -791,12 +794,21 @@ if (($MSmode == 5) or ($MSmode == 4))
|
|
|
}
|
|
|
else
|
|
|
{
|
|
|
- placeTextWithLink($pos_y+31,$pos_x-15, sprintf('%.2F mA', $I_PR), 60, 2, $color, "Current through post regulation triode shunt. 0.46-0.8 mA for optimal performance.", $adeiChannel[10][28]);
|
|
|
- placeTextWithLink($pos_y+45,$pos_x-14, sprintf('%2.0F W', $P_PR), 60, 2, $color, "Power consumption of post regulation triode shunt. Must be < 28 W.", $adeiChannel[10][28]);
|
|
|
+ placeTextWithLink($pos_y+31,$pos_x-15, sprintf('%.2F mA', $I_PR), 60, 2, $color,
|
|
|
+ "Current through post regulation triode shunt. 0.46-0.95 mA as long as power < 28 W for optimal performance.",
|
|
|
+ $adeiChannel[10][28]);
|
|
|
+
|
|
|
+ placeTextWithLink($pos_y+45,$pos_x-14, sprintf('%2.0F W', $P_PR), 60, 2, $color,
|
|
|
+ "Power consumption of post regulation triode shunt. Must be < 28 W to prevent damage to triode.",
|
|
|
+ $adeiChannel[10][28]);
|
|
|
|
|
|
- if ($APR_on) placeTextWithLink($pos_y+57,$pos_x-4, "APR ON", 40, 0, "#40AA40", "Advanced Post Regulation (APR) status.", $adeiChannel[10][29]);
|
|
|
+ if ($APR_on) placeTextWithLink($pos_y+57,$pos_x-4, "APR ON", 40, 0, "#40AA40",
|
|
|
+ "Advanced Post Regulation (APR) status. 
Correction at ".sprintf('%.2F %', 10*$PID_setpoint).".",
|
|
|
+ $adeiChannel[10][29]);
|
|
|
|
|
|
- if ($PID_setpoint > 9.0) placeTextWithLink($pos_y+66,$pos_x-54, "APR setpoint limit", 140, 0, "#FF0000", "APR setpoint at 90% of limit.", $adeiChannel[10][30]);
|
|
|
+ if ($PID_setpoint > 9.0) placeTextWithLink($pos_y+66,$pos_x-54,
|
|
|
+ "APR setpoint limit", 140, 0, "#FF0000",
|
|
|
+ "APR setpoint at 90% of limit.", $adeiChannel[10][30]);
|
|
|
}
|
|
|
|
|
|
} // end of PCS7 mode switch
|